Title
Power factor improvement of three‐phase unbalanced loads with non‐sinusoidal supply voltage
Document Type
Article
Publication Date
1-1-1993
Abstract
Three‐phase load asymmetry causes a useless current loading of the supply source and this loading increases even more if the supply voltage is non‐sinusoidal. This loading can be expressed quantitatively with the unbalanced current iu of RMS value ||iu||. A whole compensation of the unbalanced current iu was proved to be possible with reactive balancing circuits, however, it may be very complex. This paper shows that a substantial minimization of the unbalanced current iu may be achieved with such a circuit, but of much lower complexity. The method suggested requires that the unbalanced admittances An of the load for harmonic frequencies are known. A harmonic analysis that provides the complex RMS values of the phase voltages and currents harmonics in a cross‐section between the load and the source enables us to determine these admittances and design the balancing circuit. It was shown, moreover, that the reduction of the unbalanced current iu can be integrated with the reactive current ir minimization. Copyright © 1993 John Wiley & Sons, Ltd.
Publication Source (Journal or Book title)
European Transactions on Electrical Power
First Page
67
Last Page
74
Recommended Citation
Czarnecki, L. (1993). Power factor improvement of three‐phase unbalanced loads with non‐sinusoidal supply voltage. European Transactions on Electrical Power, 3 (1), 67-74. https://doi.org/10.1002/etep.4450030111